A SERIES

RACKBOX A1

Liquid cooling container infrastructure products

32 NVIDIA HGX H100/H200 servers can be installed

Simultaneously adapt to other cold plate liguid cooling servers

Contact Us

Product Details

    Designed as a 40 feet container system. Capable of convenient transportation, outdoor modular rapid deployment, and strong adaptability to harsh environments.

    The RACKBOX A1 container system contains 8 independent racks inside, each of which can carry 4 cold plate NVIDIA HGX H100/H200 servers and is compatible with other cold plate liquid cooled servers. 

    The entire system can provide hosting space for 32 NVIDIA servers, totaling 256 H100/H200/GPU graphics cards.


Option 1


Item

Parameter

Structure

Container Dimension (L×D×H)

12192mm×3000mm×2896mm

Qty. of Rack

8

Qty. of HGX H100 Servers/Rack

4

Qty. of HGX H100

256

FP16 Operation Speed

506,624 TFLOPS

Weight

≤ 20t (Excluding IT equipment)

Power

Power Density IT/Container

384kW

Power Density IT/Rack

48kW

Power Supply Architecture

2N

Power Supply

Dual power supply

Input

380/400/415V, 50/60Hz

UPS

400kVA*2N

Battery

Lithium, Back up 7.5min

HVAC

Final Heat Rejection

Cooling Tower

Cooling Tower Capacity

300KW*2N

Internal circulation

Propylene glycol mixture

External circulation

Ethylene glycol mixture

Air Cooling

40kW*(3+1), DX In-row

Cold Aisle Temperature

10℃~30℃

Humidity

20%RH~80%RH

Management

T&H Sensor

Support

Water Leakage Sensor

Support

Access Control

Support

Video

2 million-pixel network camera

NVR

Stored for 1-3 months

Fire Protection

Fire Extinguishing System

Automatic Gas Fire Extinguishing System,includes temperature detectors, audible and visual alarms, gas fire extinguishing controllers, and fire gas cylinders etc

Fire Protection Performance

Fire resistance within 60 min. The protective
structure is made of flame-retardant level-A1 rock wool materials

Others

Waterproof and Dustproof

IP55

Anti-corrosion

1440 hours salt spray test equirements

Theft Prevention

The anti-theft level meets the requirement of EN-1627~EN 1630 Class 3


Option 2

Genre

Item

Parameter

Structure 

Container Dimension (L×D×H)

12192mm×3000mm×2896mm

Qty. of Rack

8

Qty. of HGX H100 Servers/Rack

4

Qty. of HGX H100

256

FP16 Running Speed

506,624 TFLOPS

Weight

≤ 20t (Excluding IT equipment)

Power

Power Density IT/Container

384kW

Power Density IT/Rack

48kW

Power Supply Architecture

2N

Power Supply

Dual power supply

Input

380/400/415V, 50/60Hz

UPS

400kVA*2N

Battery

Lithium, Back up 7.5min

Environment

Dissipation Method

Cooling Tower or Dry Cooler

Heat Dissipation Capacity

300KW*2N

Coolant of Internal Circulation 

Ethylene glycol/propylene glycol mixture

Coolant of External Circulation

Ethylene glycol mixture

Air Cooling Parts

40kW*(3+1), DX In-row AC

Cold Aisle Temperature

10℃~30℃

Humidity

20%RH~80%RH

Management

Temp & Humidity Sensor

Support

Water Leakage Sensor

Support

Access Control

Support

Video

3 million-pixel network camera

NVR

Stored for 1-3 months

Fire Protection

Fire Extinguishing System

Automatic Gas Fire Extinguishing System, includes temperature detectors, audible and visual alarms, gas fire extinguishing controllers, and fire gas cylinders etc.

Fire Protection Performance 

Fire resistance within 60 min. The protective structure is made of flame-retardant level- A1 rock wool materials

Others

Waterproof an Dustproof

IP55

Seismic Resistance

ETSI EN 300 019-2-4 Zone 4

Anti-corrosion

1440 hours salt spray test requirements

Theft Prevention

The anti-theft level meets the requirement of EN-1627~EN 1630 Class 3

Next: AIRBOX-A1